MOXA ICF-1150-M-SC

ICF-1150-M-SCIndustrial serial-to-fiber converters SC MM

The ICF-1150 series support 2 serial ports, with a D-sub connector for RS-232 communication and a removable terminal block for RS-422 or RS-485 communication. The 3 ports (2 serial ports and one fiber port) are completely independent. When an ICF-1150 converter receives data from any one port, it will send the data out through the other 2 ports. For example, once the ICF-1150 converter receives a command from the remote master through the fiber port, it will convert the signal and send the command through the RS-232 and RS-422/485 ports at the same time. If the user is monitoring a system running on an RS-485 network, there is no need to use an additional RS-232 to RS-485 converter to connect the laptop computer’s serial port to the RS-485 bus.

Rotary Switch for Setting the Pull High/Low Resistor

The RS-485 interface supports multi-drop or daisy-chain connections, which system engineers will use to connect serial devices such as meters, RTUs, and readers together on the same bus. Since the number of serial devices on the same bus will cause the impedance of the data line to increase, the ICF-1150 allows users to tune the pull high/low resistor. Just rotate the switch to the appropriate value without removing the ICF-1150 from the DIN-rail.

Feature :

Features and Benefits

  • RS-232, fiber, and RS-422/485 3-way communication
  • Rotary switch to change the pull high/low resistor value
  • Extend RS-232/422/485 transmission up to:
  •   40 km with single-mode
  •   5 km with multi-mode3-way Galvanic Isolation (for “I” model only)
  • 40 to 85°C wide temperature models available
  • C1D2, ATEX, and IECEx certified for harsh industrial environments

Diagram :

Diagram ICF-1150-M-SC-1

Diagram ICF-1150-M-SC-2

Specification :

• Optical Fiber Side
Fiber Connector SC or ST
Cable Requirements Single-mode: 8.3/125, 8.7/125, 9/125, or 10/125 μm
Multi-mode: 50/125, 62.5/125, or 100/140 μm
Transmission Distance Single-mode: 40 km
Multi-mode: 5 km
Wavelength ICF-1150-S (single-mode): 1310 nm
ICF-1150-M (multi-mode): 850 nm
Tx Output ICF-1150-S (single-mode): > -5 dBm
ICF-1150-M (multi-mode): > -5 dBm
Rx Sensitivity ICF-1150-S (single-mode): -25 dBm
ICF-1150-M (multi-mode): -20 dBm
Point-to-Point Transmission Half-duplex or full-duplex
Ring Transmission Half-duplex
• RS-232/422/485 Side
RS-232 Signals TxD, RxD, GND
RS-422 Signals TxD+, TxD-, RxD+, RxD-, GND
RS-485-4w Signals TxD+, TxD-, RxD+, RxD-, GND
RS-485-2w Signals Data+, Data-, GND
Baudrate 50 bps to 921.6 Kbps
ESD Protection 15 kV for all signals
Isolation 2 kV RMS isolation per I/O port for 1 minute
• Physical Characteristics
Housing Metal
Dimensions 30.3 x 70 x 115 mm (1.19 x 2.76 x 4.53 in)
Weight 330 g
• Environmental Limits
Operating Temperature Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
• Power Requirements
Input Voltage 12 to 48 VDC
Power Consumption ICF-1150: 127 mA @ 12 V
ICF-1150I: 163 mA @ 12 V
Voltage Reversal Protection Protects against V+/V- reversal
Over Current Protection 1.1 A (protects against two signals shorted together)
• Standards and Certifications
Safety UL 508
Hazardous Location UL/cUL Class I Division 2 Groups A/B/C/D, ATEX Zone 2 EEx nC IIC, IECEx
EMC CE, FCC
EMI EN 55022 Class B, FCC Part 15 Subpart B Class B
EMS EN 61000-4-2 (ESD) Level 4,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 4,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (PFMF) Level 3
Freefall IEC 60068-2-32
Green Product RoHS, CRoHS, WEEE
• MTBF (mean time between failures)
Time 792,085 hrs
Database Telcordia (Bellcore), GB
Water and Dust Proof IP30
• Warranty
Warranty Period 5 years
Details See http://www.moxa.com/support/warranty.htm

MOXA TCF-142-S-SC

TCF-142-S-SCRS-232/422/485 to optical fiber media converters SC SM

The TCF-142 media converter is equipped with a multiple interface circuit that can handle RS-232 or RS-422/485 serial interfaces and multi-mode or single-mode fiber. TCF-142 converters are used to extend serial transmission up to 5 km (TCF-142-M with multi-mode fiber) or up to 40 km (TCF-142-S with single-mode fiber). The TCF-142 can be configured to convert either RS-232 signals, or RS-422/485 signals, but not both at the same time.

Automatic Baudrate Detection

The TCF-142 can automatically detect the serial baudrate. This is an extremely convenient feature. Even if a device’s baudrate is changed, the signal will still be transmitted through the media converter without any data loss.

Ring Operation

The TCF-142 converters can be used to connect serial devices to a fiber ring. To form the ring, connect the Tx port of one TCF-142 to the Rx port of a neighboring converter. Once the ring is set up, simply use the DIP switches to configure the TCF-142 converters for “ring mode.” When one node transmits a signal, the signal travels around the ring until it returns back to the transmitting unit, which then blocks the signal. With the TCF-142, you can set up fiber rings that have a total circumference of up to 100 km.

Automatic Data Direction Control (ADDC®)

ADDC® is a patented hardware data flow solution developed by Moxa to handle RS-485 data direction control. ADDC® senses and controls RS-485 data direction automatically, making it unnecessary to use the hand shaking signal.

Feature :

Features and Benefits 

  • “Ring” and “Point-to-Point” transmission
  • Extends RS-232/422/485 transmission up to:
    • 40 km with single-mode—TCF-142-S
    • 5 km with multi-mode—TCF-142-M
  • Compact size
  • Decreases signal interference
  • Protects against electrical interference and chemical corrosion
  • Supports baudrates of 50 bps to 921.6 Kbps
  • Wide temperature models available (-40 to 75°C)

Diagram :

Diagram TCF-142-S-SC

Specification :

• Optical Fiber Side
Fiber Connector SC or ST
Cable Requirements Single-mode: 8.3/125, 8.7/125, 9/125, or 10/125 μm
Multi-mode: 50/125, 62.5/125, or 100/140 μm
Transmission Distance Single-mode: 40 km
Multi-mode: 5 km
Wavelength Single-mode: 1310 nm
Multi-mode: 850 nm
Tx Output Single-mode: > -5 dBm
Multi-mode: > -5 dBm
Rx Sensitivity Single-mode: -25 dBm
Multi-mode: -20 dBm
Point-to-Point Transmission Half-duplex or full-duplex
Ring Transmission Half-duplex
• RS-232/422/485 Side
Connector Terminal Block
RS-232 Signals Tx, Rx, GND
RS-422 Signals TxD+, TxD-, RxD+, RxD-, GND
RS-485-4w Signals TxD+, TxD-, RxD+, RxD-, GND
RS-485-2w Signals Data+, Data-, GND
Baudrate 50 bps to 921.6 Kbps
ESD Protection 15 KV for all signals
• Physical Characteristics
Housing Aluminum (1 mm)
Dimensions Without ears: 67 x 100 x 22 mm (2.64 x 3.94 x 0.87 in)
With ears: 90 x 100 x 22 mm (3.54 x 3.94 x 0.87 in)
Weight 320 g
• Environmental Limits
Operating Temperature Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 75°C (-40 to 167°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
• Power Requirements
Input Voltage 12 to 48 VDC
Power Consumption 140 mA @ 12 V
Power Line Protection 2 KV Burst (EFT), EN61000-4-4
2 KV Surge, EN61000-4-5
Voltage Reversal Protection Protects against V+/V- reversal
Over Current Protection 1.1 A (protects against two signals shorted together)
• Standards and Certifications
Safety UL 60950-1
EMC CE, FCC
EMI FCC Part 15 Subpart B Class B, EN 55022 Class B
EMS EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 2,
EN 61000-4-5 (Surge) Level 2,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (SFMF) Level 1
Green Product RoHS, CRoHS, WEEE
• MTBF (mean time between failures)
Time 780,480 hrs
Database Telcordia (Bellcore), GB
• Warranty
Warranty Period 5 years
Details See http://www.moxa.com/support/warranty.htm

MOXA TCF-142-M-ST

TCF-142-M-STRS-232/422/485 to optical fiber media converters ST MM

The TCF-142 media converter is equipped with a multiple interface circuit that can handle RS-232 or RS-422/485 serial interfaces and multi-mode or single-mode fiber. TCF-142 converters are used to extend serial transmission up to 5 km (TCF-142-M with multi-mode fiber) or up to 40 km (TCF-142-S with single-mode fiber). The TCF-142 can be configured to convert either RS-232 signals, or RS-422/485 signals, but not both at the same time.

Automatic Baudrate Detection

The TCF-142 can automatically detect the serial baudrate. This is an extremely convenient feature. Even if a device’s baudrate is changed, the signal will still be transmitted through the media converter without any data loss.

Ring Operation

The TCF-142 converters can be used to connect serial devices to a fiber ring. To form the ring, connect the Tx port of one TCF-142 to the Rx port of a neighboring converter. Once the ring is set up, simply use the DIP switches to configure the TCF-142 converters for “ring mode.” When one node transmits a signal, the signal travels around the ring until it returns back to the transmitting unit, which then blocks the signal. With the TCF-142, you can set up fiber rings that have a total circumference of up to 100 km.

Automatic Data Direction Control (ADDC®)

ADDC® is a patented hardware data flow solution developed by Moxa to handle RS-485 data direction control. ADDC® senses and controls RS-485 data direction automatically, making it unnecessary to use the hand shaking signal.

Feature :

Features and Benefits 

  • “Ring” and “Point-to-Point” transmission
  • Extends RS-232/422/485 transmission up to:
    • 40 km with single-mode—TCF-142-S
    • 5 km with multi-mode—TCF-142-M
  • Compact size
  • Decreases signal interference
  • Protects against electrical interference and chemical corrosion
  • Supports baudrates of 50 bps to 921.6 Kbps
  • Wide temperature models available (-40 to 75°C)

Diagram :

Diagram TCF-142-M-ST

Specification :

• Optical Fiber Side
Fiber Connector SC or ST
Cable Requirements Single-mode: 8.3/125, 8.7/125, 9/125, or 10/125 μm
Multi-mode: 50/125, 62.5/125, or 100/140 μm
Transmission Distance Single-mode: 40 km
Multi-mode: 5 km
Wavelength Single-mode: 1310 nm
Multi-mode: 850 nm
Tx Output Single-mode: > -5 dBm
Multi-mode: > -5 dBm
Rx Sensitivity Single-mode: -25 dBm
Multi-mode: -20 dBm
Point-to-Point Transmission Half-duplex or full-duplex
Ring Transmission Half-duplex
• RS-232/422/485 Side
Connector Terminal Block
RS-232 Signals Tx, Rx, GND
RS-422 Signals TxD+, TxD-, RxD+, RxD-, GND
RS-485-4w Signals TxD+, TxD-, RxD+, RxD-, GND
RS-485-2w Signals Data+, Data-, GND
Baudrate 50 bps to 921.6 Kbps
ESD Protection 15 KV for all signals
• Physical Characteristics
Housing Aluminum (1 mm)
Dimensions Without ears: 67 x 100 x 22 mm (2.64 x 3.94 x 0.87 in)
With ears: 90 x 100 x 22 mm (3.54 x 3.94 x 0.87 in)
Weight 320 g
• Environmental Limits
Operating Temperature Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 75°C (-40 to 167°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
• Power Requirements
Input Voltage 12 to 48 VDC
Power Consumption 140 mA @ 12 V
Power Line Protection 2 KV Burst (EFT), EN61000-4-4
2 KV Surge, EN61000-4-5
Voltage Reversal Protection Protects against V+/V- reversal
Over Current Protection 1.1 A (protects against two signals shorted together)
• Standards and Certifications
Safety UL 60950-1
EMC CE, FCC
EMI FCC Part 15 Subpart B Class B, EN 55022 Class B
EMS EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 2,
EN 61000-4-5 (Surge) Level 2,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (SFMF) Level 1
Green Product RoHS, CRoHS, WEEE
• MTBF (mean time between failures)
Time 780,480 hrs
Database Telcordia (Bellcore), GB
• Warranty
Warranty Period 5 years
Details See http://www.moxa.com/support/warranty.htm

MOXA A53-DB9F

A53-DB9FEntry-Level RS-232 to RS-422/485 Converters

The Transio A52 and A53 are smart RS-232 to RS-422/485 bi-directional converters that come with all of the great technical specs that Moxa is known for. This includes data direction control built into the hardware for both the RS-422 and RS-485 interfaces, LED indicators for power and signal states, and surge protection and isolation protection. The last two features take care of some of the major problems faced by serial communication connections in industrial environments.

Serial Connection Problems in Industrial Environments

Serial communication and reliability can be adversely affected in a hazardous industrial environment. The wiring associated with serial communication devices could be surrounded by power lines, motors, or equipment that produces static electricity. If this is the case, the serial devices could be damaged by sudden surge waves produced by this type of equipment. In this situation, surge protection that uses TVSS (Transient Voltage Surge Supression) is the solution.

When two serial devices are directly connected, but separated by a long distance, the unbalanced ground voltage could cause serious damage. Unbalanced ground voltage between two serial ports forms a “ground loop,” introducing a large current between the two pieces of serial equipment. In fact, the current could be so lare as to damage the equipment beyond repair. In this situation, the solution is to use isolation protection to provide complete isolation for both communication ports.

What is Surge Protection?

Surges are high amplitude pulses that last only a few millionths of a second in duration. They can be caused by heavy-duty equipment, power lines, short circuits, or large motors. A surge suppressor has the ability to absorb the high energy instantly and effectively to prevent the connected devices from being damaged.

What is Isolation Protection?

Electrical isolation is achieved by using a photo coupler to transform an electric signal into light, and then retransform the light back into an electric signal on the other side of the isolator. In this way, the two electric circuits are completely isolated from each other.

Feature :

Features and Benefits

  • ADDC™ (Automatic Data Direction Control) RS-485 data control
  • Auto baudrate sensing
  • RS-422 hardware flow control: CTS, RTS signals
  • LED indicators for power and signal states
  • RS-485 multidrop operation, up to 32 nodes
  • 25 KV ESD surge protection
  • 2 KV isolation protection (A53)
  • Built-in 120 Ω termination resistors

Specification :

• Serial Communication
RS-232 Signals Tx, Rx, DTR, DSR, RTS, CTS, DCD, GND (RJ45)
RS-422/485 Signals Supports RS-422, 2-wire RS-485 (DIP switch selectable)
Supports 4-wire RS-422, up to 10 nodes, 1.2 km with RTS, CTS
Supports 2-wire RS-485, up to 32 nodes, 1.2 km
Optical Isolation Protection 2 KV (A53), power/signal
Power EFT/Surge Protecction 25 KV ESD surge protection
• RS-422/485 Side
RS-485 Data Direction Control ADDC™
• Serial Transmission
Baudrate 50 bps to 230.4 Kbps
• Physical Characteristics
Housing ABS
Weight 85 ± 5 g
Dimensions 90 x 60 x 21 mm
• Environmental Limits
Operating Temperature 0 to 55°C (32 to 131°F)
Operating Humidity 5 to 95% RH
Storage Temperature -20 to 75°C (-4 to 167°F)
• Power Requirements
Input Voltage 9 to 30 VDC, 350 mA
Power Consumption A52: 170 mA @ 9 V
A53: 285 mA @ 9 V
Over Current Protection Protection against 2 signals shorted together
• Regulatory Approvals
CE Class A
FCC Class A
• Warranty
Warranty Period 5 years
Details See http://www.moxa.com/support/warranty.htm

MOXA TCC-100I

TCC-100IIndustrial RS-232 to RS-422/485 converters with 2 KV isolation

The TCC-100 and TCC-100I are RS-232 to RS-422/485 converters that increase networking capability by extending the RS-232 transmission distance. Both converters have a superior industrial-grade design that includes DIN-rail mounting, terminal block wiring, external terminal block for power, and optical isolation (TCC-100I only). The TCC-100/100I are ideal solutions for converting RS-232 signals to RS-422/485 in critical industrial environments.

Feature :

Features and Benefits

  • RS-232 to RS-422 conversion with RTS/CTS support
  • RS-232 to 2-wire or 4-wire RS-485 conversion
  • 2 KV isolation protection (TCC-100I/TCC-100I-T)
  • Wall and DIN-rail mounting
  • Plug-in terminal block for easy RS-422/485 wiring
  • LED indicators for power, Tx, Rx
  • -20 to 60°C operating temperature
  • Wide temperature model available (-40 to 85°C )

Diagram :

Diagram TCC-100I-1

Diagram TCC-100I-2

Specification :

• RS-232 Side
Connector DB9 female
Signals TxD, RxD, RTS, CTS, GND
• RS-422/485 Side
Connector Terminal Block
Signals (interface selected by DIP switch)
RS-422: TxD+, TxD-, RxD+, RxD-, RTS, CTS, GND
RS-485-4w: TxD+, TxD-, RxD+, RxD-, GND
RS-485-2w: Data+, Data-, GND
RS-485 Data Direction Control ADDC® (automatic data direction control)
• Serial Communication
Baudrate 50 bps to 921.6 Kbps
ESD Protection 15 KV
Optical Isolation 2 KV (TCC-100I/100I-T)
• Physical Characteristics
Housing Aluminum
Dimensions 67 x 100.4 x 22 mm (2.64 x 3.93 x 0.87 in)
Weight 148 ± 5 g
• Environmental Limits
Operating Temperature Standard Models: -20 to 60°C (-4 to 140°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
• Power Requirements
Source of Input Power Power input jack
Input Voltage 12 to 48 VDC
Power Consumption TCC-100/100-T: 85 mA @ 12 V
TCC-100I/100I-T: 150 mA @ 12 V
Voltage Reversal Protection Protects against V+/V- reversal
Over Current Protection Protects against two signals shorted together
• Standards and Certifications
Safety UL 60950-1
EMC CE, FCC
EMI FCC Part 15 Subpart B Class B
EMS IEC 61000-4-2 (ESD) Level 2,
IEC 61000-4-3 (RS) Level 2,
IEC 61000-4-4 (EFT) Level 2,
IEC 61000-4-5 (Surge) Level 2,
IEC 61000-4-6 (CS) Level 2,
IEC 61000-4-8 (SFMF) Level 1
Green Product RoHS, CRoHS, WEEE
• MTBF (mean time between failures)
Time 3,017,857 hrs
Database MIL-HDBK-217F
• Warranty
Warranty Period 5 years
Details See http://www.moxa.com/support/warranty.htm