MOXA MGate MB3270

MGate MB32702-port advanced serial-to-Ethernet Modbus gateways

The MB3170 and MB3270 are advanced Modbus gateways that provide maximum flexibility for integrating industrial Modbus networks of all types and sizes. They are designed to integrate Modbus TCP, ASCII, and RTU devices in almost any master and slave combination, including serial master to serial slave, or simultaneous serial and Ethernet masters. A special priority control feature allows urgent commands to obtain immediate response. All models are ruggedly constructed, are DIN-rail mountable, and offer built-in optical isolation for serial signals as an option.

Integration of TCP masters without alteration to Modbus RTU/ASCII network or software

The MB3270 can integrate Modbus TCP with Modbus RTU/ASCII,without modifying the existing Modbus RTU/ASCII architecture or software. With the serial redirector function, a serial master can maintain direct access to serial slave devices through a specially mapped serial port. This allows the serial and TCP masters to access serial slaves simultaneously.

Cascading Ethernet ports for easy wiring

Advanced models of the MGate™ MB3000 series have two Ethernet ports to make network wiring easier. Dual Ethernet ports allow users to string multiple Modbus gateways together using standard RJ45 Ethernet cables, eliminating the need for a separate Ethernet switch.

Redundant power inputs

Advanced models of the MB3000 series have dual power inputs for greater reliability. The power inputs allow simultaneous connections to two live DC power sources, so that continuous operation is provided even if one power source fails. The higher level of reliability makes these advanced Modbus gateways ideal for demanding industrial applications.

Warning by relay output

A relay output is provided for the Ethernet link and power input status. The relay output gives maintenance engineers an additional tool for troubleshooting and maintenance.

Priority control for urgent commands (Patented)

As Modbus networks increase in size and complexity, the lag time between commands and responses becomes a major concern. Advanced models of the MB3000 series provide a priority control function for urgent commands, allowing users to force certain commands to get an immediate response. Depending on your system’s requirements, different methods are available to define which commands receive priority.

Feature :

Features and Benefits 

  • Configuration is exceptionally easy Download Moxa's MGate Gateway Brochure and White Paper
  • Slave mode supports 16 TCP masters and up to 62 serial slaves at the same time
  • Master mode supports 32 TCP slaves at the same time
  • Emergency request tunnels ensure QoS control
  • Serial redirector function provided
  • Embedded Modbus protocol analyzer
  • Redundant dual DC power inputs
  • Built-in Ethernet cascading for easy wiring
  • Supports Moxa’s MXview industrial network management software via the MXview Plug-in

* MGate MB3170/3270 Modbus gateway has received Taiwan Excellence and Good Design awards.

Diagram :

Diagram MGate MB3270

Specification :

• Ethernet Interface
Protocol Modbus TCP
Number of Ports 2 (1 IP, Ethernet cascade)
Speed 10/100 Mbps, Auto MDI/MDIX
Connector 8-pin RJ45
Magnetic Isolation Protection 1.5 kV (built-in)
• Serial Interface
Protocol Modbus RTU/ASCII Slave/Master
Number of Ports MB3170/3170I: 1
MB3270/3270I: 2
Serial Standards RS-232/422/485, software selectable
Connectors MB3170/3170I: DB9 male for RS-232, terminal block for RS-422/485
MB3270/3270I: DB9 male x 2
ESD Protection 15 kV for all signals
RS-485 Data Direction Control ADDC® (automatic data direction control)
Pull High/Low Resistor for RS-485 1 kΩ, 150 kΩ
Terminator for RS-485 120 Ω
• Serial Communication Parameters
Data Bits 7, 8
Stop Bits 1, 2
Parity None, Even, Odd, Space, Mark
Flow Control RTS/CTS, DTR/DSR (RS-232 only)
Baudrate 50 bps to 921.6 kbps
• Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
• Software
Configuration Options Web Console, Serial Console, Telnet Console, Windows Utility
Utility MGate Manager for Windows 2000/XP/2003/Vista/Server 2008/7/8 (x86/x64), Windows Server 2008 R2/2012 (x64)
Multi-master and Multi-drop Master mode: 32 TCP slaves
Slave mode: 16 TCP masters (request queue 32-deep for each master)
Support Smart Routing, Serial Redirection, ProCOM, Priority Control, MXview, SNMP v1 (read only)
• Physical Characteristics
Housing Plastic
Weight MGate MB3170: 360 g
MGate MB3270: 380 g
Dimensions Without ears: 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)
With ears extended: 29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in)
• Environmental Limits
Operating Temperature Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m (795 hPa), higher altitudes on demand
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Power Requirements
Input Voltage 12 to 48 VDC
Power Connector Terminal block
Power Consumption MGate MB3170: 435 mA (max.)
MGate MB3170I: 555 mA (max.)
MGate MB3270: 435 mA (max.)
MGate MB3270I: 510 mA (max.)
Relay Output 1 digital relay output to alarm (normal close): Current carrying capacity 1 A @ 30 VDC
• Standards and Certifications
Safety UL 508, EN 60950-1
Hazardous Location UL/cUL Class 1 Division 2 Groups A/B/C/D,
ATEX Zone 2 Ex nA IIC T3 Gc, IECEx (-IEX model only)
EMC CE, FCC
EMI EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS EN 55024,
EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 3,
EN 61000-4-4 (EFT) Level 4,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 3,
EN 61000-4-8 (PFMF) Level 1,
EN 61000-4-11
Marine DNV
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6
• Reliability
MTBF (mean time between failures) MGate MB3170: 210,794 hrs
MGate MB3270: 125,234 hrs
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty

MOXA MGate MB3170

MGate MB31701-port advanced serial-to-Ethernet Modbus gateways

The MB3170 and MB3270 are advanced Modbus gateways that provide maximum flexibility for integrating industrial Modbus networks of all types and sizes. They are designed to integrate Modbus TCP, ASCII, and RTU devices in almost any master and slave combination, including serial master to serial slave, or simultaneous serial and Ethernet masters. A special priority control feature allows urgent commands to obtain immediate response. All models are ruggedly constructed, are DIN-rail mountable, and offer built-in optical isolation for serial signals as an option.

Integration of TCP masters without alteration to Modbus RTU/ASCII network or software

The MB3270 can integrate Modbus TCP with Modbus RTU/ASCII,without modifying the existing Modbus RTU/ASCII architecture or software. With the serial redirector function, a serial master can maintain direct access to serial slave devices through a specially mapped serial port. This allows the serial and TCP masters to access serial slaves simultaneously.

Cascading Ethernet ports for easy wiring

Advanced models of the MGate™ MB3000 series have two Ethernet ports to make network wiring easier. Dual Ethernet ports allow users to string multiple Modbus gateways together using standard RJ45 Ethernet cables, eliminating the need for a separate Ethernet switch.

Redundant power inputs

Advanced models of the MB3000 series have dual power inputs for greater reliability. The power inputs allow simultaneous connections to two live DC power sources, so that continuous operation is provided even if one power source fails. The higher level of reliability makes these advanced Modbus gateways ideal for demanding industrial applications.

Warning by relay output

A relay output is provided for the Ethernet link and power input status. The relay output gives maintenance engineers an additional tool for troubleshooting and maintenance.

Priority control for urgent commands (Patented)

As Modbus networks increase in size and complexity, the lag time between commands and responses becomes a major concern. Advanced models of the MB3000 series provide a priority control function for urgent commands, allowing users to force certain commands to get an immediate response. Depending on your system’s requirements, different methods are available to define which commands receive priority.

Feature :

Features and Benefits 

  • Configuration is exceptionally easy Download Moxa's MGate Gateway Brochure and White Paper
  • Slave mode supports 16 TCP masters and up to 62 serial slaves at the same time
  • Master mode supports 32 TCP slaves at the same time
  • Emergency request tunnels ensure QoS control
  • Serial redirector function provided
  • Embedded Modbus protocol analyzer
  • Redundant dual DC power inputs
  • Built-in Ethernet cascading for easy wiring
  • Supports Moxa’s MXview industrial network management software via the MXview Plug-in

* MGate MB3170/3270 Modbus gateway has received Taiwan Excellence and Good Design awards.

Diagram :

Diagram MGate MB3170

Specification :

• Ethernet Interface
Protocol Modbus TCP
Number of Ports 2 (1 IP, Ethernet cascade)
Speed 10/100 Mbps, Auto MDI/MDIX
Connector 8-pin RJ45
Magnetic Isolation Protection 1.5 kV (built-in)
• Serial Interface
Protocol Modbus RTU/ASCII Slave/Master
Number of Ports MB3170/3170I: 1
MB3270/3270I: 2
Serial Standards RS-232/422/485, software selectable
Connectors MB3170/3170I: DB9 male for RS-232, terminal block for RS-422/485
MB3270/3270I: DB9 male x 2
ESD Protection 15 kV for all signals
RS-485 Data Direction Control ADDC® (automatic data direction control)
Pull High/Low Resistor for RS-485 1 kΩ, 150 kΩ
Terminator for RS-485 120 Ω
• Serial Communication Parameters
Data Bits 7, 8
Stop Bits 1, 2
Parity None, Even, Odd, Space, Mark
Flow Control RTS/CTS, DTR/DSR (RS-232 only)
Baudrate 50 bps to 921.6 kbps
• Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
• Software
Configuration Options Web Console, Serial Console, Telnet Console, Windows Utility
Utility MGate Manager for Windows 2000/XP/2003/Vista/Server 2008/7/8 (x86/x64), Windows Server 2008 R2/2012 (x64)
Multi-master and Multi-drop Master mode: 32 TCP slaves
Slave mode: 16 TCP masters (request queue 32-deep for each master)
Support Smart Routing, Serial Redirection, ProCOM, Priority Control, MXview, SNMP v1 (read only)
• Physical Characteristics
Housing Plastic
Weight MGate MB3170: 360 g
MGate MB3270: 380 g
Dimensions Without ears: 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)
With ears extended: 29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in)
• Environmental Limits
Operating Temperature Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m (795 hPa), higher altitudes on demand
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Power Requirements
Input Voltage 12 to 48 VDC
Power Connector Terminal block
Power Consumption MGate MB3170: 435 mA (max.)
MGate MB3170I: 555 mA (max.)
MGate MB3270: 435 mA (max.)
MGate MB3270I: 510 mA (max.)
Relay Output 1 digital relay output to alarm (normal close): Current carrying capacity 1 A @ 30 VDC
• Standards and Certifications
Safety UL 508, EN 60950-1
Hazardous Location UL/cUL Class 1 Division 2 Groups A/B/C/D,
ATEX Zone 2 Ex nA IIC T3 Gc, IECEx (-IEX model only)
EMC CE, FCC
EMI EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS EN 55024,
EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 3,
EN 61000-4-4 (EFT) Level 4,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 3,
EN 61000-4-8 (PFMF) Level 1,
EN 61000-4-11
Marine DNV
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6
• Reliability
MTBF (mean time between failures) MGate MB3170: 210,794 hrs
MGate MB3270: 125,234 hrs
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty

MOXA MGate MB3480

MGate MB34804 Port RS-232/422/485 Modbus TCP to Serial Comunication Gateway

The MB3180, MB3280, and MB3480 are standard Modbus gateways that convert between Modbus TCP and Modbus RTU/ASCII protocols. Up to 16 simultaneous Modbus TCP masters are supported, with up to 31 RTU/ASCII slaves per serial port. For RTU/ASCII masters, up to 32 TCP slaves are supported.

Standard Modbus network integration
MGate MB3000 standard models include the MB3180, MB3280, and MB3480, and are designed for easy integration of Modbus TCP and RTU/ASCII networks. With these models, Modbus serial slave devices can be seamlessly incorporated into an existing Modbus TCP network, and Modbus TCP slaves can be made accessible to serial masters. The MB3180, MB3280, andMB3480 offer features that make network integration easy, customizable, and compatible with almost any Modbus network.

High density, cost effective gateway
The MGate MB3000 can effectively integrate networks with a high density of Modbus nodes. The MB3280 can manage up to 62 serial slave nodes, whereas the MB3480 can manage 124. Each RS-233/422/485 serial port can be individually configured for Modbus RTU or Modbus ASCII operation or even different baudrate, allowing both types of networks to be integrated with Modbus TCP within one package.

Feature :

Features and Benefits 

  • Convert between Modbus TCP and Modbus RTU/ASCII  Download Moxa's MGate Gateway Brochure and White Paper
  • 1 Ethernet port and 1, 2, or 4 RS-232/422/485 ports
  • Supports 16 simultaneous TCP masters with up to 32 simultaneous requests per master
  • Easy hardware setup and configuration
  • Supports Moxa’s MXview industrial network management software via the MXview Plug-in

Diagram :

Diagram MGate MB3480-1

Diagram MGate MB3480-2

Specification :

• Ethernet Interface
Protocol Modbus TCP
Number of Ports 1
Speed 10/100 Mbps, Auto MDI/MDIX
Connector 8-pin RJ45
Magnetic Isolation Protection 1.5 kV (built-in)
• Serial Interface
Protocol Modbus RTU/ASCII Slave/Master
Number of Ports MB3180: 1
MB3280: 2
MB3480: 4
Serial Standards RS-232/422/485, software selectable
Connectors DB9 male
ESD Protection 15 kV for all signals
RS-485 Data Direction Control ADDC® (automatic data direction control)
• Serial Communication Parameters
Data Bits 7, 8
Stop Bits 1, 2
Parity None, Even, Odd, Space, Mark
Flow Control RTS/CTS, DTR/DSR (RS-232 only)
Baudrate 50 bps to 921.6 kbps
• Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
• Software
Configuration Options Web Console, Serial Console, Telnet Console, Windows Utility
Utilities MGate Manager for Windows 2000/XP/2003/Vista/Server 2008/7/8 (x86/x64), Windows Server 2008 R2/2012 (x64)
Multi-master and Multi-drop Master mode: 32 TCP slaves
Slave mode: 16 TCP masters (request queue 32-deep for each master)
Support Smart Routing, MXview, SNMP v1 (read only)
• Physical Characteristics
Housing Metal, IP30 protection
Weight MGate MB3180: 340 g
MGate MB3280: 360 g
MGate MB3480: 740 g
Dimensions Without ears:
MB3180: 22 x 52 x 80 mm (0.87 x 2.05 x 3.15 in)
MB3280: 22 x 77 x 111 mm (0.87 x 3.03 x 4.37 in)
MB3480: 35.5 x 102.7 x 157.2 mm (1.40 x 4.04 x 6.19 in)
With ears:
MB3180: 22 x 75 x 80 mm (0.87 x 2.95 x 3.15 in)
MB3280: 22 x 100
• Environmental Limits
Operating Temperature 0 to 55°C (32 to 131°F)
Storage Temperature -20 to 70°C (-4 to 158°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m (795 hPa), higher altitudes on demand
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Power Requirements
Input Voltage 12 to 48 VDC
Power Connector MGate MB3180: Power jack
MGate MB3280/3480: Power jack and terminal block
Power Consumption MGate M3180: 200 mA (max.)
MGate M3280: 250 mA (max.)
MGate M3480: 385 mA (max.)
• Standards and Certifications
Safety UL 60950-1, EN 60950-1
EMC CE, FCC
EMI EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS EN 55024,
EN 61000-4-2 (ESD) Level 2,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 2,
EN 61000-4-5 (Surge) Level 2,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (PFMF) Level 1,
EN 61000-4-11
• Reliability
MTBF (mean time between failures) MGate M3180: 628,376 hrs
MGate M3280: 503,029 hrs
MGate M3480: 295,812 hrs
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty

MOXA MGate MB3280

MGate MB32802 Port RS-232/422/485 Modbus TCP to Serial Comunication Gateway

The MB3180, MB3280, and MB3480 are standard Modbus gateways that convert between Modbus TCP and Modbus RTU/ASCII protocols. Up to 16 simultaneous Modbus TCP masters are supported, with up to 31 RTU/ASCII slaves per serial port. For RTU/ASCII masters, up to 32 TCP slaves are supported.

Standard Modbus network integration
MGate MB3000 standard models include the MB3180, MB3280, and MB3480, and are designed for easy integration of Modbus TCP and RTU/ASCII networks. With these models, Modbus serial slave devices can be seamlessly incorporated into an existing Modbus TCP network, and Modbus TCP slaves can be made accessible to serial masters. The MB3180, MB3280, andMB3480 offer features that make network integration easy, customizable, and compatible with almost any Modbus network.

High density, cost effective gateway
The MGate MB3000 can effectively integrate networks with a high density of Modbus nodes. The MB3280 can manage up to 62 serial slave nodes, whereas the MB3480 can manage 124. Each RS-233/422/485 serial port can be individually configured for Modbus RTU or Modbus ASCII operation or even different baudrate, allowing both types of networks to be integrated with Modbus TCP within one package.

Feature :

Features and Benefits 

  • Convert between Modbus TCP and Modbus RTU/ASCII  Download Moxa's MGate Gateway Brochure and White Paper
  • 1 Ethernet port and 1, 2, or 4 RS-232/422/485 ports
  • Supports 16 simultaneous TCP masters with up to 32 simultaneous requests per master
  • Easy hardware setup and configuration
  • Supports Moxa’s MXview industrial network management software via the MXview Plug-in

Diagram :

Diagram MGate MB3280-1

Diagram MGate MB3280-2

Specification :

• Ethernet Interface
Protocol Modbus TCP
Number of Ports 1
Speed 10/100 Mbps, Auto MDI/MDIX
Connector 8-pin RJ45
Magnetic Isolation Protection 1.5 kV (built-in)
• Serial Interface
Protocol Modbus RTU/ASCII Slave/Master
Number of Ports MB3180: 1
MB3280: 2
MB3480: 4
Serial Standards RS-232/422/485, software selectable
Connectors DB9 male
ESD Protection 15 kV for all signals
RS-485 Data Direction Control ADDC® (automatic data direction control)
• Serial Communication Parameters
Data Bits 7, 8
Stop Bits 1, 2
Parity None, Even, Odd, Space, Mark
Flow Control RTS/CTS, DTR/DSR (RS-232 only)
Baudrate 50 bps to 921.6 kbps
• Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
• Software
Configuration Options Web Console, Serial Console, Telnet Console, Windows Utility
Utilities MGate Manager for Windows 2000/XP/2003/Vista/Server 2008/7/8 (x86/x64), Windows Server 2008 R2/2012 (x64)
Multi-master and Multi-drop Master mode: 32 TCP slaves
Slave mode: 16 TCP masters (request queue 32-deep for each master)
Support Smart Routing, MXview, SNMP v1 (read only)
• Physical Characteristics
Housing Metal, IP30 protection
Weight MGate MB3180: 340 g
MGate MB3280: 360 g
MGate MB3480: 740 g
Dimensions Without ears:
MB3180: 22 x 52 x 80 mm (0.87 x 2.05 x 3.15 in)
MB3280: 22 x 77 x 111 mm (0.87 x 3.03 x 4.37 in)
MB3480: 35.5 x 102.7 x 157.2 mm (1.40 x 4.04 x 6.19 in)
With ears:
MB3180: 22 x 75 x 80 mm (0.87 x 2.95 x 3.15 in)
MB3280: 22 x 100
• Environmental Limits
Operating Temperature 0 to 55°C (32 to 131°F)
Storage Temperature -20 to 70°C (-4 to 158°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m (795 hPa), higher altitudes on demand
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Power Requirements
Input Voltage 12 to 48 VDC
Power Connector MGate MB3180: Power jack
MGate MB3280/3480: Power jack and terminal block
Power Consumption MGate M3180: 200 mA (max.)
MGate M3280: 250 mA (max.)
MGate M3480: 385 mA (max.)
• Standards and Certifications
Safety UL 60950-1, EN 60950-1
EMC CE, FCC
EMI EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS EN 55024,
EN 61000-4-2 (ESD) Level 2,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 2,
EN 61000-4-5 (Surge) Level 2,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (PFMF) Level 1,
EN 61000-4-11
• Reliability
MTBF (mean time between failures) MGate M3180: 628,376 hrs
MGate M3280: 503,029 hrs
MGate M3480: 295,812 hrs
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty

MOXA MGate MB3180

Mgate MB31801 Port RS-232/422/485 Modbus TCP to Serial Comunication Gateway

The MB3180, MB3280, and MB3480 are standard Modbus gateways that convert between Modbus TCP and Modbus RTU/ASCII protocols. Up to 16 simultaneous Modbus TCP masters are supported, with up to 31 RTU/ASCII slaves per serial port. For RTU/ASCII masters, up to 32 TCP slaves are supported.

Standard Modbus network integration
MGate MB3000 standard models include the MB3180, MB3280, and MB3480, and are designed for easy integration of Modbus TCP and RTU/ASCII networks. With these models, Modbus serial slave devices can be seamlessly incorporated into an existing Modbus TCP network, and Modbus TCP slaves can be made accessible to serial masters. The MB3180, MB3280, andMB3480 offer features that make network integration easy, customizable, and compatible with almost any Modbus network.

High density, cost effective gateway
The MGate MB3000 can effectively integrate networks with a high density of Modbus nodes. The MB3280 can manage up to 62 serial slave nodes, whereas the MB3480 can manage 124. Each RS-233/422/485 serial port can be individually configured for Modbus RTU or Modbus ASCII operation or even different baudrate, allowing both types of networks to be integrated with Modbus TCP within one package.

Feature :

Features and Benefits 

  • Convert between Modbus TCP and Modbus RTU/ASCII  Download Moxa's MGate Gateway Brochure and White Paper
  • 1 Ethernet port and 1, 2, or 4 RS-232/422/485 ports
  • Supports 16 simultaneous TCP masters with up to 32 simultaneous requests per master
  • Easy hardware setup and configuration
  • Supports Moxa’s MXview industrial network management software via the MXview Plug-in

Diagram :

Diagram MGate MB3180-1

Diagram MGate MB3180-2

Specification :

• Ethernet Interface
Protocol Modbus TCP
Number of Ports 1
Speed 10/100 Mbps, Auto MDI/MDIX
Connector 8-pin RJ45
Magnetic Isolation Protection 1.5 kV (built-in)
• Serial Interface
Protocol Modbus RTU/ASCII Slave/Master
Number of Ports MB3180: 1
MB3280: 2
MB3480: 4
Serial Standards RS-232/422/485, software selectable
Connectors DB9 male
ESD Protection 15 kV for all signals
RS-485 Data Direction Control ADDC® (automatic data direction control)
• Serial Communication Parameters
Data Bits 7, 8
Stop Bits 1, 2
Parity None, Even, Odd, Space, Mark
Flow Control RTS/CTS, DTR/DSR (RS-232 only)
Baudrate 50 bps to 921.6 kbps
• Serial Signals
RS-232 TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422 Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w Data+, Data-, GND
• Software
Configuration Options Web Console, Serial Console, Telnet Console, Windows Utility
Utilities MGate Manager for Windows 2000/XP/2003/Vista/Server 2008/7/8 (x86/x64), Windows Server 2008 R2/2012 (x64)
Multi-master and Multi-drop Master mode: 32 TCP slaves
Slave mode: 16 TCP masters (request queue 32-deep for each master)
Support Smart Routing, MXview, SNMP v1 (read only)
• Physical Characteristics
Housing Metal, IP30 protection
Weight MGate MB3180: 340 g
MGate MB3280: 360 g
MGate MB3480: 740 g
Dimensions Without ears:
MB3180: 22 x 52 x 80 mm (0.87 x 2.05 x 3.15 in)
MB3280: 22 x 77 x 111 mm (0.87 x 3.03 x 4.37 in)
MB3480: 35.5 x 102.7 x 157.2 mm (1.40 x 4.04 x 6.19 in)
With ears:
MB3180: 22 x 75 x 80 mm (0.87 x 2.95 x 3.15 in)
MB3280: 22 x 100
• Environmental Limits
Operating Temperature 0 to 55°C (32 to 131°F)
Storage Temperature -20 to 70°C (-4 to 158°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m (795 hPa), higher altitudes on demand
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Power Requirements
Input Voltage 12 to 48 VDC
Power Connector MGate MB3180: Power jack
MGate MB3280/3480: Power jack and terminal block
Power Consumption MGate M3180: 200 mA (max.)
MGate M3280: 250 mA (max.)
MGate M3480: 385 mA (max.)
• Standards and Certifications
Safety UL 60950-1, EN 60950-1
EMC CE, FCC
EMI EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS EN 55024,
EN 61000-4-2 (ESD) Level 2,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 2,
EN 61000-4-5 (Surge) Level 2,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (PFMF) Level 1,
EN 61000-4-11
• Reliability
MTBF (mean time between failures) MGate M3180: 628,376 hrs
MGate M3280: 503,029 hrs
MGate M3480: 295,812 hrs
• Warranty
Warranty Period 5 years
Details See www.moxa.com/warranty