Feature :

Features and Benefits

  • Active communication with patented Active OPC Server
  • Two independent Ethernet LANs
  • Allow up to 16-module expansion without needing a backplane
  • Front-end intelligence with patented Click&Go control logic up to
    80 rules
  • Smart alarm management with e-mail, SNMP Trap, TCP, UDP
  • Friendly configuration via web browser
  • Simplify I/O management with MXIO library on Windows or Linux
    platform
  • Support SNMPv1/v2c protocol

Introduction

The ioLogik E4200 is suitable for remote monitoring and alarm systems, such as are used for water treatment systems, water supply systems, wastewater treatment systems, and power monitoring systems. These kinds of applications need more I/O points and a variety of I/O types, including temperature sensors, gas detectors, and water quality detectors, all of which can benefit from the versatile mixture of I/O features supported by the ioLogik E4200.

 

Slice Form Factor and Flexible I/O Combination

The unique modular construction of the ioLogik E4200 allows the mixing and matching of modules to achieve the best combination of I/O modules to meet the needs of a wide range of remote automation applications. The ioLogik E4200 features an industrial modular housing that allows up to 16 I/O modules to be added to the base unit without a backplane. The width of each module is merely 12 mm, and at a full load of 16 modules, the total size is less than 25 cm—perfect for space-limited applications. The ioLogik E4200 provides up to 256 DI/DO points or 64 AI/AO points for greater flexibility and expandability. The modules can connect to virtually any type of sensor, including but not limited to those for temperature, pressure, flow, voltage, current, and contact closure.

 

Two Independent Ethernet LANs

ioLogik E4200 modular remote I/O comes with dual network interfaces with separate MAC and IP addresses for connecting to different network segments. The two independent Ethernet LANs improve system reliability by allowing hosts located on different networks to control and monitor the remote I/O units.

 

Click&Go™ Code-free Local Intelligent Control

The patented Click&Go event-based control logic offers local control without the need to communicate with the remote host. Click&Go’s intuitive, graphical interface and simple IF-THEN-ELSE control logic, which defines how the ioLogik E4200 will respond to different events, is easy and straightforward to set up. Click&Go supports active communication methods, including TCP, UDP, SNMP Trap, email, and CGI commands, making it extremely easy to integrate Click&Go with any monitoring system.

Diagram :

Specification :

• LAN
Ethernet 2 x 10/100 Mbps: 2 MACs, 2 IPs, RJ45 connectors
Protection 1.5 kV magnetic isolation
Protocols Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, HTTP, SNTP, SMTP
• Serial Communication
Interface 1 x RS-232 (9-pin D-Sub, male)
Parameters N, 8, 1
Baudrate 115,200 bps
• Power Requirements
Power Input 24 VDC nominal, 12 to 36 VDC
Power Consumption 175 mA @ 24 VDC
Current for I/O Modules Max. 1.5A @ 5 VDC
• Field Power
Rated Voltage 11 to 28.8 VDC, 24 VDC typical
Current in Field Power Contact Max. 10 A
• Isolation
System Power to I/O Driver Optical isolation, 3k VDC or 2k Vrms
• Physical Characteristics
Dimensions 45 x 99 x 70 mm (1.77 x 3.90 x 2.76 in)
Note Please see pages 15-23 for the dimensions diagram.
Weight 180 g
Mounting DIN rail
• Environmental Limits
Operating Temperature -10 to 60°C (14 to 140°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
Altitude Up to 2000 m
Note Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
• Standards and Certifications
Safety UL 508
EMI 61000-3-2; EN 61000-3-3; EN 61000-6-4; FCC Part 15, Subpart B, Class A
EMS EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6, EN 61000-4-8,
EN 61000-6-2, IEC 61000-4-11
Shock IEC 60068-2-27
Freefall IEC 60068-2-32
Vibration IEC 60068-2-6
Green Product RoHS, CRoHS, WEEE
Note Please check Moxa’s website for the most up-to-date certification status.
• MTBF (mean time between failure)
Time 357,000 hrs
Database Telcordia (Bellcore)
• Warranty
Warranty Period 2 years
Details See www.moxa.com/warranty