Ethernet Peer-to-Peer I/O with 8 digital inputs and 8 digital outputs
Direct Input-to-Output Communication over IP
ioMirror E3000 Ethernet I/O products are designed as a cablereplacement solution that connects remote digital input signals to output signals over an IP network. The ioMirror E3210 provides 8 digital input channels, 8 digital output channels, and a 10/100M Ethernet interface. Up to 8 pairs of digital input and output signals can be exchanged over Ethernet with another ioMirror E3210, or can be sent to a local PLC or DCS controller. Over a local area network, the ioMirror can achieve a low signal latency (typically less than 20 ms). With ioMirror, remote sensors can now be connected to local controllers or display panels over copper, fiber, or wireless Ethernet infrastructures. Signals can be transmitted over virtually unlimited distances, without noise problems.
Split Sensor Signals to 16 Different Locations
The ioMirror E3000 can split one input signal to two digital output channels at two different IP addresses. Eight tank level signals can be monitored at 16 different display panels, all at the same time.
Local Alarm and Remote Alarm Messages for Monitoring Connectivity
The ioMirror E3210 has a 24 VDC alarm output channel that can activate an attached buzzer or LED display when the connection fails. In addition, both ioMirror modules can send messages to the ioEventLog software, ensuring that at least one of the warning messages will reach the ioEventLog software
Feature :
The Green Core Product Identity of the ioMirror series will be phased in starting May 1, 2014. During the product transition period, you may still receive products that use the previous panel design. Please click here to learn more about Moxa’s Green Core product transition.
Features and Benefits
- Direct input-to-output signal communication over IP
- High speed Peer-to-Peer I/O within 20 ms
- One physical alarm port for connectivity status
- Quick and easy utility and web-based settings
- Local alarm channel
- Remote alarm message
- Supports Modbus/TCP for remote monitoring
- Optional LCD module for simple setting
Diagram :
Specification :
• Inputs and Outputs | |
Digital Inputs | 8 channels |
Digital Outputs | 8 channels |
Alarm Port Output | 1 channel |
• Digital Input | |
Sensor Type | Wet Contact (NPN), Dry Contact |
I/O Mode | Digital Input |
Dry Contact | • On: short to GND
• Off: open |
Wet Contact (source type) | • On: 0 to 3 VDC
• Off: 10 to 30 VDC |
Common Type | 8 points per COM |
Isolation | 3K VDC or 2K Vrms |
Digital Filtering Time Interval | Software selectable |
Over-voltage Protection | 36 VDC |
• Digital Output | |
Type | Sink |
I/O Mode | Digital Output |
Over-voltage Protection | 45 VDC |
Over-current Protection | 2.6 A (4 channels @ 650 mA) |
Over-temperature Shutdown | 160°C |
Current Rating | 200 mA per channel |
Isolation | 3K VDC or 2K Vrms |
• Alarm Port Output | |
Current Rating | 200 mA per channel |
Isolation | 3K VDC or 2K Vrms |
• LAN | |
Ethernet | 1 x 10/100 Mbps, RJ45 |
Protection | 1.5 KV magnetic isolation |
Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP, SNTP |
• Power Requirements | |
Power Input | 24 VDC nominal, 12 to 48 VDC |
DO Power | 24 VDC nominal, up to 45 VDC |
Power Consumption | 136 mA @ 24 VDC |
• Physical Characteristics | |
Wiring | I/O cable max. 14 AWG |
Dimensions | 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in) |
Weight | 205 g |
• Environmental Limits | |
Operating Temperature | -10 to 60°C (14 to 140°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Altitude | Up to 2000 m and higher altitude on demand |
• Standards and Certifications | |
Safety | UL 508 |
EMI | FCC Part 15 Subpart B Class A, EN 55022 Class A |
EMS | IEC 61000-4, IEC 61000-6 |
Shock | IEC 60068-2-27 |
Freefall | IEC 60068-2-32 |
Vibration | IEC 60068-2-6 |
• Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |