IEC 61850-3 and EN 50155 Ethernet-to-fiber media converters multi-mode with SC connector, 1 isolated power supply
The PTC-101 Ethernet-to-fiber media converters convert from 10/100BaseT(X) to 100BaseFX. Models are available with either SC, ST, or LC connectors. The PTC-101 converters eliminate the need for additional wiring, and support IEEE 802.3 and IEEE 802.3u/x protocols with 10/100M, full/half-duplex, and MDI/MDI-X auto-sensing to provide a total solution for your industrial Ethernet networks. The PTC-101 is compliant with the essential sections of EN 50155, covering operating temperature, power input voltage, surge, ESD and vibration.
Feature :
- 10/100BaseT(X) auto-negotiation and auto-MDI/MDI-X
- Link Fault Pass-Through (LFP)
- Power failure alarm by relay output (LV model only)
- -40 to 85°C operating temperature range
- Redundant dual DC power inputs
- Integrated high-reliability power supply eliminates the need for external power transformer
- Compliant with EN 50121-4 and essential sections of EN 50155
Diagram :
Specifation :
Standards | IEEE 802.3 for 10BaseT IEEE 802.3u for 100BaseT(X), 100BaseFX |
• Interface | |
RJ45/M12 Ports | 10/100BaseT(X) |
Fiber Ports | 100BaseFX (SC/ST/LC connectors) |
LED Indicators | PWR1, PWR2, Fiber Link, 10/100M (TP port) |
DIP Switches | |
Alarm Contact | One relay output with current carrying capacity of 1 A @ 24 VDC (LV model only) |
• Optical Fiber | |
Table | |
• Physical Characteristics | |
Housing | Metal, IP30 protection |
Dimensions | 152.15 x 123.46 x 66.65 mm (5.99 x 4.86 x 2.62 in) |
Weight | Product only: 690 g Packaged: 875 g |
• Environmental Limits | |
Operating Temperature | -40 to 85°C (-40 to 185°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Conformal Coating | Available upon request |
• Power Requirements | |
Input Voltage | |
Note | LV-DC compliant with EN 50155 on 48VDC HV-DC compliant with EN 50155 on 110VDC |
Connection | Removable terminal block |
Overload Current Protection | 1.6 A (protects against two signals shorted together) |
Reverse Polarity Protection | Protects against V+/V- reversal |
• Standards and Certifications | |
Safety | UL 60950-1 |
EMC | CE, FCC |
EMI | FCC Part 15 Subpart B Class A, EN 55022 Class A |
EMS | EN 61000-4-2 (ESD) Level 4, EN 61000-4-3 (RS) Level 3, EN 61000-4-4 (EFT) Level 4, EN 61000-4-5 (Surge) Level 4, EN 61000-4-6 (CS) Level 3, EN 61000-4-8 (PFMF) Level 5, EN 61000-4-11 |
Power Automation | IEC 61850-3, IEEE 1613 |
Rail Traffic | EN 50155, EN 50121-4 |
Freefall | IEC 60068-2-32 |
Vibration | IEC-61850-3, IEC-60870-2-2 |
Green Product | RoHS, CRoHS, WEEE |
Note | Refer to the “Environmental Type Tests” table below for more detailed information. |
• MTBF (mean time between failures) | |
Time | 1,211,613 hrs |
Database | Telcordia (Bellcore), GB |
• Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |