PE7216As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE7216 eco PDUs are intelligent PDUs that contain 16 AC outlets and are available in various IEC socket configurations.NRGence eco PDUs provide secure, centralized, intelligent, power management (power on, off, cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center’s health environment via sensors.NRGence eco PDUs offer remote power control combined with real-time power measurement — allowing you to control and monitor the power status of devices attached to the PDUs, either at the PDU device, bank, or outlet level, depending on the model, from practically any location via a TCP/IP connection.

NRGence eco PDU supports any 3rd party V3 SNMP Manager Software and NRGence eco Sensors (eco PDU Manager Software). eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it.With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable, and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible.

Feature :

  • Connections
  • Support 10/100Mbit Ethernet Interface
  • Support TCP/IP, UDP, HTTP, HTTPS, SSL, DHCP, SMTP, NTP, DNS, Auto Sense, Ping, SNMP V1,V2&V3
  • Support 2-level account/password security, IP/MAC filter, 128 bit SSL, RADIOUS
  • Support : eco Sensors, Browser ( IE, Firefox, Chrome, Safari )
  • Metering
  • PDU and outlet level power metering and monitoring
  • Environment monitoring – supports external temperature/temperature & humidity sensors for rack temperature and humidity monitoring
  • Current, voltage, power, power dissipation, temperature, and humidity metering and threshold level setting
  • Support door sensor
  • Outlet Switch Control
  • Always On

Diagram :Diagram PE7216Specification :

Function PE7216B PE7216G
Electrical
Nominal Input Voltage 100 – 240 VAC
Maximum Input Current 20A Max ; 16A (UL de-rated) 16A Max
Input Frequency 50-60 Hz
Input Connection 1 x NEMA 6-20P 1 x IEC60320 C20
Input Power 4160 VA(Max) 3328 VA (UL de-rated) 3680 VA(Max)
Outlet Type Total : 14 x IEC320 C13 + 2 x IEC320 C19
Bank1-1 : Outlet 1 – 8 ; 7 x C13 + 1 x C19
Bank1-2 : Outlet 9 – 16 ; 7 x C13 + 1 x C19
Nominal Output Voltage 100 – 240 VAC
Maximum Output Current (Outlet) C13 : 15A (Max) 12A(UL de-rated)
C19 : 20A (Max) 16A(UL de-rated)
C13 : 10A (Max)
C19 : 16A (Max) , TUV De-rated 15A(Max)
Maximum Output Current (Bank) 20A(Max) 16A (UL de-rated) 16A(Max), TUV De-rated 15A(Max)
Maximum Output Current (Total) 20A(Max) 16A (UL de-rated) 16A(Max). TUV De-rated 15A(Max)
Breakers 1 x 20A Non-Fuse breaker 1 x 16A Non-Fuse breaker
Metering Per Outlet Level Current, Voltage, VA, PF, KWh Monitoring
Outlet Switch None
Environment Sensor Port 4
Metering Accuracy Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ 5000W +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Mechanical
Dimension (H x W x D) 132.5 x 6.6 x 4.4 cm 132.5 x 6.6 x 4.4 cm
Weight 3.7 kg 3.7 kg
Power Cord Length 1.6 m
Environmental
Temperature (Operating / Storage) 0 – 50°C / -20 – 60°C 0 – 40°C / -20 – 60°C
Humidity (Operating & Storage) 0 – 80% RH, Non-Condensing
Compliance
EMC Verication FCC Part 15 Class A, Others by Reuest CE, Others by Request
Safety Verication TUV-CB, Others by Reuest TUV-CB, CE-LVD, Others by Request
  • The specification and pictures are subject to change without notice.
  • All trademarks and logos are the properties of their respective holders.