PE6208-eco-PDUs-OL-large

• 8 outlets
• 20A (UL derated 16A) / 16A
• PDU Power Measurement
The PE6208 eco PDU is intelligent PDUs that contains 8 AC outlets and is available in various IEC or NEMA socket configurations. It provides secure, centralized, intelligent, power management (power on, off, cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center’s health environment via sensors*.

The eco PDUs offer remote power control combined with real-time power measurement – allowing you to control and monitor the power status of devices attached to the PDUs at the PDU device level from practically any location via a TCP/IP connection.

The eco PDU supports any 3rd party v3 SNMP Manager Software and the eco Sensors (Energy Management Software). The eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it. With the eco Sensors, the Sensor-enabled eco PDU also offers comprehensive power analysis reports which can separate by departments and locations, providing precise measurements of current, voltage, power and watt-hour in a real-time display.

With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable, and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible.

*Sensors are optional accessories. A sensor-enabled installation is required to generate a more complete energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data.

Features :

  • Power Distribution
  • Space saving 1U rack mount design with rear mounting
  • IEC or NEMA outlet models
  • 3 digit 7-segment front panel LED shows Current / IP Address
  • Remote users can monitor outlet status via web pages on their browsers
  • Safe shutdown support
  • Separate power for the unit’s own power and its power outlets. The user interface is still accessible even when an overload condition trips the devices’ circuit breakerRemote Access
  • Remote power control via TCP/IP and a built in 10/100 Ethernet port
  • Network Interfaces: TCP/IP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP, NTP, DNS, 10Base-T/100Base-TX, auto sense, Ping, Telnet
  • eco PDU Power Management software – eco Sensors
  • Supports SNMP Manager V3Operation
  • Remote power outlet control (On, Off, Power Cycle) by individual outlets
  • Power-on sequencing – users can set the power on sequence and delay time for each port to allow equipment to be turned on in the proper order
  • Easy setup and operation via a browser-based user interface
  • Multibrowser support (IE, Firefox, Chrome, Safari)
  • RTC support to keep the timer running during times of no power.
  • Supports up to 8 user and 1 administrator accounts
  • Proactive Overload Protection (POP) – automatically powers off outlets when current overloads to protect operating devicesManagement
  • Power status measurement at the PDU or Outlet level
  • LED indicators for current and IP address at the PDU device level
  • Real-time current, voltage, and kWH displayed in a browsed-based UI for monitoring at the PDU level
  • Current and voltage threshold setting
  • Naming support for outlets
  • User outlet access assignment on an outlet-by-outlet basis.
  • Event logging and syslog support
  • Upgradeable firmware
  • Multilanguage support: English, German, Traditional Chinese, Simplified Chinese, Japanese, French, Spanish, ItalianSecurity
  • Power status measurement at the PDU or
  • Two-level password security
  • Strong security features include password protection and advanced encryption technologies – 128 bit SSL
  • Remote authentication support: RADIUSeco Sensors Energy Management Software
  • Automatic discovery of all PE devices within the same intranet
  • Remote real-time power measurement and monitoring
  • Remote real-time power outlet management*
  • Remote real-time environment sensor monitoring
  • Plotting/Monitoring of all PE devices
  • Exceed threshold alert through SMTP and Syslog
  • Power Analysis Report

Diagram :

PE6208-eco-PDUs-dg-org

Specification :

Power Distribution Unit

 

Function PE6208A PE6208B PE6208G
Electrical
Nominal Input Voltage 100 – 120 VAC 100 – 240 VAC 100 – 240 VAC
Maximum Input Current 20A Max; 16A(UL de-rated) 20A Max; 16A(UL de-rated) 16A Max
Input Frequency 50-60 Hz 50-60 Hz 50-60 Hz
Input Connection NEMA 5-20P NEMA 6-20P IEC 60320 C20
Input Power 2400 VA(Max); 1920 VA(UL de-rated) 4160 VA(Max); 3328 VA(UL de-rated) 3680 VA(Max)
Outlet Type Total : 8 x NEMA 5-20R Total : 7 x IEC320 C13 + 1 x IEC320 C19 Total : 7 x IEC320 C13 + 1 x IEC320 C19
Nominal Output Voltage 100 – 120 VAC 100 – 240 VAC 100 – 240 VAC
Maximum Output Current (Outlet) NEMA 5-20R: 20A(Max); 16A(UL de-rated) C13: 15A(Max); 12A(UL de-rated)
C19: 20A(Max); 16A(UL de-rated)
C13: 10A(Max)
C19: 16A(Max)
Maximum Output Current (Bank) 20A(Max); 16A(UL de-rated) 20A(Max); 16A(UL de-rated) 16A(Max)
Maximum Output Current (Total) 20A(Max); 16A(UL de-rated) 20A(Max); 16A(UL de-rated) 16A(Max)
Breakers 1 x 20A Non-Fuse Breaker 1 x 20A Non-Fuse Breaker 1 x 16A Non-Fuse Breaker
Metering Bank level Current, Voltage, VA , PF and KWh Monitoring Bank level Current, Voltage, VA , PF and KWh Monitoring Bank level Current, Voltage, VA , PF and KWh Monitoring
Outlet Switching Yes Yes Yes
Environment Sensor Ports 2 2 2
Metering Accuracy Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Voltage Range: 100VAC ~ 250VAC +/-1%
Power Range: 100W ~ Maximum Capacity +/- 2%
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1%
Physical Properties
Dimensions (L x W x H) 43.24 x 22.04 x 4.40 cm
(17.02 x 8.68 x 1.73 in.)
43.24 x 22.04 x 4.40 cm
(17.02 x 8.68 x 1.73 in.)
43.24 x 22.04 x 4.40 cm
(17.02 x 8.68 x 1.73 in.)
Weight 2.79 kg ( 6.15 lb ) 2.79 kg ( 6.15 lb ) 2.79 kg ( 6.15 lb )
Power Cord Length 3 m 3 m 3 m
Environmental
Temperature (Operating / Storage) 0 – 50°C / -20 – 60°C 0 – 50°C / -20 – 60°C 0 – 50°C / -20 – 60°C
Humidity (Operating & Storage) 0 – 80% RH, Non-Condensing 0 – 80% RH, Non-Condensing 0 – 80% RH, Non-Condensing
Compliance
EMC Verification FCC, Others by Request FCC, Others by Request CE, Others by Request
Safety Verification TUV-CB, cTUVus, Others by Request TUV-CB, cTUVus, Others by Request TUV-CB, CE-LVD, Others by Request